RH_R

Dwyer Series RH-R Humidity/Temperature Transmitter

$ 248.00$ 259.00

Clear selection
SKU: N/A Categories: ,

Product Description

Remote Mount, Field Replaceable Sensor Filter, Up to 16′ Cable

The Series RH-R Humidity Transmitter is the ideal transmitter for those applications where space is limited. The compact sensor is protected by a removable filter. It can be mounted up to 16 feet away from the weatherproof base. The Series RH-R is ideal for environmental chambers, rubber bladder burst detection and air handler applications.

Models

Model Description
RHT-R008 Humidity/Temperature Transmitter, 8′ cable, current output.
RHT-R016 Humidity/Temperature Transmitter, 16′ cable, current output.
RHT-R108 Humidity/Temperature Transmitter, 8′ cable, voltage output.
RHT-R116 Humidity/Temperature Transmitter, 16′ cable, voltage output.
RHU-R008 Humidity Transmitter, 8′ cable, current output.
RHU-R016 Humidity Transmitter, 16′ cable, current output.
RHU-R108 Humidity Transmitter, 8′ cable, voltage output.

Specifications

Service:
Dry Clean Air.
Relative Humidity Range:
0 to 100% RH.
Temperature Range:
-40 to 140°F (-40 to 60°C).
Accuracy:
±2% @ 10-90%.
Temperature Limits:
-40 to 140°F (-40 to 60°C).
Storage Temperature:
-40 to 176°F (-40 to 80°C).
Compensated Temperature Range:
-4 to 140°F (-20 to 60°C).
Power Requirements:
10-35 VDC.
Output Signal:
4-20 mA loop powered or 0 to 10 VDC.
Response Time:
Less than 15 seconds.
Electrical Connections:
Terminal block.
Conduit Connection:
1/2″ NPT.
Process Connection:
1/2 NPSM.
Drift:
Less than 1%/year.
RH Sensor:
Capacitance polymer.
Cable Length:
Up to 16 ft.
Housing Material:
Polycarbonate, aluminum enclosure.
Enclosure Rating:
NEMA 4X (IP65).
Agency Approvals:
CE.

Literature

Manuals

RH-R

Catalog Pages

Series RH-R Catalog Page

Drawings

Adobe Reader in format .PDF
CAD Drawing in format .DWG

Model Chart

EXAMPLE RHT R0 04 Series RHT-R004 Temperature/Humidity Transmitter, 4-20 mA output, with 4 ft. cable.
SERIES RHT
RHU
    Temperature/Humidity Transmitter
Humidity Transmitter
OUTPUT   R0
R1
  Current 4-20 mA
Voltage 0-10 V
CABLE LENGTH     04
08
12
16
4 Ft.
8 Ft.
12 Ft.
16 Ft.

FAQ

Question
I’m looking for a dual temp. and humidity gauge for an 8″ duct. I’m wanting to remote read the temp and humidity on the incoming and outgoing air to an ERV unit. The RHP-3M11-LCD was recommended to me, however, it is a direct read. What would be the correct instrument to remote read the temperature and humidity from a distance of 8 feet. The 8″ duct is in the attic and I want to read the result in the down-stair hall. I don’t want to record nor program the unit, just read the performance.
Answer
The sensor recommended would be the best option we have for sensing temperature and relative humidity for your application. We do not have any options with a remote display that could stretch as far as you are asking, nor are there any on the market to my knowledge. In every case, you would need to utilize a process output, in this case 4-20 mA, to transmit the readings to a remote display(s) which would accept the process signal(s). If you are just looking for a remote readout to go with the RHP sensor with no control functionality, then you could look at one of our panel meters, possibly the SPPM, DPMA, DPMW, or DPMP & DPML series panel meters. For assistance selecting an appropriate panel meter, please contact our technical support group at 219-879-8000.